After adding the APC UPS to be monitored in Ncentral. It shows as misconfigured and I receive the following error after adding the APC UPS monitoring.

NCentral Error: 102 Value not found for specified interface : upsAdvBatteryReplaceIndicator

 

by
edited by

1 Answer

0 votes
 
Best answer

I faced the same problem and set everything below to make sure that the monitoring in n-central would work correctly for the APC UPS monitor.

  • Install APC and made sure that I could manage the UPS from the APC console
  • Install the SNMP service on the server
  • Configure the SNMP service to allow connections from the probe.